Magnetic type, oil filled, single bushing Voltage Transformer
Applicable Specifications ANSI C57.13
89kV NSU, 350 BIL, 60Hz
Primary Volts 40,250 L-G (69,000 L-L)
ANSI Group 3
Ratios 600/350 & 600/350:1
Secondary volts 67.08/115 & 67.08/115
5.0 KVA @ 30C ambient
Accuracy 0.3, burdens 0 to ZZ
Thermal Rating 6000VA
Creepage Distance to Ground 51
With secondary terminal box
Weight SHALL be less than 550 pounds each.