The RFP Database
New business relationships start here

636-17-2-8891-0364 SIX-YEAR FIRE DAMPER INSPECTION


South Dakota, United States
Government : Federal
RFP
Go to the link
This document has expired, therefore the above link may no longer work.

This is a sources sought notice only and it is not a solicitation announcement. The purpose of this sources sought notice is to gain knowledge of qualified potential contractors and their socio-economic size classification in accordance with NAICS code 561621. Responses will be used by the Government to make appropriate acquisition decisions.

After a review of the responses to this sources sought notice, a solicitation announcement may be posted to Federal Business Opportunity website (www.FBO.gov). A response to this sources sought notice is not an adequate reply to the forthcoming solicitation.

Sources Sought Notice

Please fully complete each section of the survey below.

Company Name: _____________________________________________________________
Company Address: ___________________________________________________________
DUNS Number: _____________________________________________________________
Point of Contact: ____________________________________________________________
Phone Number: _____________________________________________________________
Email Address: _____________________________________________________________

Socio-economic Classification in Accordance with NAICS Code 811310: (check all that apply)
Small Business
Service Disabled Veteran Owned Small Business (SDVOSB)
Verified SDVOSB by www.vip.vetbiz.gov
Veteran Owned Small Business (VOSB)
Verified VOSB by www.vip.vetbiz.gov
Small Disadvantage Business
Women-owned Small Business
Economically Disadvantaged Small Business
HUBZone
8(a) Certified


Company s Capability Statement for Emergency Generator and Transfer Switch Maintenance: __________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________

STATEMENT OF WORK (SOW)
SMOKE & FIRE DAMPERS 6-YEAR TEST

GENERAL. Accomplish the smoke & fire dampers test that is required every six years for the Joint Commission Accreditation of Hospitals. The estimate is that 164 dampers need tested. The contractor must be able to work on and with the existing SIMPLEXGRINNEL FIRE ALARM SYSTEM; the contractor will be required to work with and on the SIMPLEXGRINNEL FIRE ALARM SYSTEM.

REFERENCES. The inspection must be accomplished to satisfy the requirements written in the following:
NFPA 80, Standard for Fire Doors and Other Opening Protectives, (2016 Edition); specifically important is Chapter 19.
The fusible link operating temperature shall be in accordance with NFPA 90A, Standard for the Installation of Air Conditioning and Ventilating Systems, and ANSI/UL 33, Standard for Heat Responsive Links for Fire-Protection Services, temperature classifications and ratings.
NFPA 101, Life Safety Code (2015 Edition), Section 8.5.5.4.

Test/Inspection Service Provided By Contractor. The Iowa City VA Medical Center will provide drawings that indicate the approximate location of smoke & fire dampers, and provide other information to support the test and inspection services of the contractor with respect to Customer s Fire and Smoke Dampers.
Operate (i.e., actuate) all Fire and Smoke Dampers in the Iowa City VA Medical Center Building #1 or otherwise identify inoperable Dampers.
Remove and reset fusible links on Dampers, to verify such Damper fully closes and if necessary, replace any fusible link that is compromised (per National Fire Protection Association Code).
As necessary, lubricate all moving parts on each Damper.
Clear each Damper of any debris that would impede such Damper s normal operation.
Coordinate with Customer s representative and local fire department to place Customer s fire alarm system in test mode if necessary to conduct inspection of the smoke Dampers.
Manually activate actuators on electric and pneumatic smoke Dampers to verify proper operation of such Damper.
If there is no existing access to a Damper, then proper size access doors will be installed to facilitate inspection (additional fee).
Identify on Customer s drawings the location of each Damper (Plotting on AutoCAD available for additional fee), along with placement of identification stickers on ceilings or other location to assist in locating such Dampers following inspection.

Report. On conclusion of the performance of the Inspection Services, the Customer will be provided with a report ( Report ), which is intended to provide Customer evidence of Damper inspection for submission to applicable agencies, such as the Joint Commission and Customer s local Authority Having Jurisdiction (AHJ), as well as Company s Insurance Company. The Report shall include:
A listing of the location of each Damper, such Damper s number, and whether such Damper passed or failed; if a Damper failed, a detailed explanation of such failure shall be provided; and
Digital photographs of each Damper before and after performance of the Inspection Services (showing each Damper opened and, where operable, closed).
A list of missing or extra dampers that don t correspond to the drawings provided by the Iowa City VA Medical Center.

Scott L Morrison
Contract Specialist
(605)336-3230 x7859

scott.morrison2@va.gov

    1. Home
    2. Articles
    3. Login or Register

    4. Search

    5. Add/Announce your RFP