TANK REQUIREMENTS:
1. CYLINDRICAL SHAPE WITH A DOMED TOP.
2. 5500 GALLON MINIMUM CAPACITY.
3. POLYETHYLENE CONSTRUCTION THAT ALLOWS THE LIQUID LEVEL TO BE SEEN THROUGH THE TANK WALLS.
4. ULTRAVIOLET (UV) STABILIZED.
5. DESIGNED FOR MINIMUM 1.65 SPECIFIC GRAVITY LIQUID.
6. EQUIPPED WITH A MINIMUM OF A 16" DIAMETER MAN WAY COVER ON THE TOP.
7. EQUIPPED WITH A VENT OF SUFFICIENT SIZE TO HANDLE 200 GPM LOADING RATE.
8. THE TANK SHALL BE EQUIPPED WITH TWO 2" PVC BULKHEAD FITTINGS. THEY WILL BE A FEMALE X FEMALE THREAD AT 0
DEGREES 6" ELEVATION WITH SUMP FOR THE OUTLET AND A FEMALE X FEMALE THREAD AT 0 DEGREES 12" ELEVATION FOR THE
INLET. INLET/OUTLET NEEDS TO BE 180 DEGREES FROM EACH OTHER.